Stabilizer Model: PSS7C
Following checks and corrections are applied during Validation and AutoCorrection.
- If Tw1 <= 0 then Tw1 = Mult*TimeStep
- If Tw2 <= 0 then Tw2 = Mult*TimeStep
- If Tw3 <= 0 then Tw3 = Mult*TimeStep
- If Tw4 <= 0 then Tw4 = Mult*TimeStep
- If Ti1 <= 0 then Ti1 = Mult*TimeStep
- If Ti2 <= 0 then Ti2 = Mult*TimeStep
- If Ti3 <= 0 then Ti3 = Mult*TimeStep
- If Ti4 <= 0 then Ti4 = Mult*TimeStep
- If K0 <= 0 then K0 = Mult*TimeStep
- If Ks1 <= 0 then Ks1 = Mult*TimeStep
- If Ks2 <= 0 then Ks2 = Mult*TimeStep
- If 0.0 < T9 < 0.5*Mult*TimeStep then T9 = 0, ElseIf 0.5*Mult*TimeStep < T9 < Mult*TimeStep then T9 = Mult*TimeStep
- If Vstmax < Vstmin then swap the values. If Vstmax < 0 then Vstmax change sign to positive. If Vstmin > 0 then change sign to negative.
- If Vsi1max < Vsi1min then swap the values.
- If Vsi2max < Vsi2min then swap the values.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| Ics1 | First stabilizer input code; 1=Rotor speed deviation (pu); 2=Bus Freq Deviation (pu); 3=Gen Pelec on Machine Base (pu); 4=Gen accelerating power (pu); 5=Bus voltage (pu); 6=Derivative of Bus voltage (pu); 7=Compensated Frequency Signal (pu) |
| Ics2 | Second stabilizer input code; 1=Rotor speed deviation (pu); 2=Bus Freq Deviation (pu); 3=Gen Pelec on Machine Base (pu); 4=Gen accelerating power (pu); 5=Bus voltage (pu); 6=Derivative of Bus voltage (pu) |
| M | PSS ramp tracking filter denominator exponent |
| N | PSS ramp tracking filter overal exponent |
| Ks1 | PSS main gain |
| Ks2 | PSS gain |
| Ks3 | PSS gain |
| T6 | PSS transducer time constant for input channel 1 |
| T7 | PSS transducer time constant for input channel 2 |
| Tw1 | First washout on first remote bus, sec |
| Tw2 | Second washout on first remote bus, sec |
| Tw3 | First washout on second remote bus, sec |
| Tw4 | Second washout on second remote bus, sec |
| T8 | PSS ramp tracking filter numerator time constant |
| T9 | PSS ramp tracking filter denominator time constant |
| K0 | PSS canoniocal gain 0 |
| K1 | PSS canoniocal gain 1 |
| K2 | PSS canoniocal gain 2 |
| K3 | PSS canoniocal gain 3 |
| K4 | PSS canoniocal gain 4 |
| Ki3 | PSS third block gain |
| Ki4 | PSS fourth block gain |
| Ti1 | PSS time constant in first block |
| Ti2 | PSS time constant in second block |
| Ti3 | PSS time constant in third block |
| Ti4 | PSS time constant in fourth block |
| Vsi1max | Input Signal 1 maximum limit |
| Vsi1min | Input Signal 1 minimum limit |
| Vsi2max | Input Signal 2 maximum limit |
| Vsi2min | Input Signal 2 minimum limit |
| VSTmax | Maximum PSS output |
| VSTmin | Minimum PSS output |
| PSSActivation | Generator MW threshold for PSS activation |
| PSSDeactivation | Generator MW threshold for PSS da-activation |
| Tpgfilt | Filter time constant for Pgen used in PSS output logic |
| Xcomp | Reactance for compensated frequency calculation |
| Tcomp | Time constant for compensated frequency calculation |